3 function set-up, 4 heated optics, Function set-up – Spectrex 40/40L-LB UV/IR Flame Detector Series User Manual

Page 43: Heated optics, Table 15: functions

Advertising
background image

TM 40/40L, Rev (6) February 2013

Configuring your Detector

31

2.8.3 Function Set-up

You can select the desired functions as detailed in Table 15.

Table 15: Functions

Function

Setting

Alarm Latch

Yes: Enable Alarm latching.

No: Disable Alarm latching (default).

Auxiliary Relay**

Yes: Activate Auxiliary Relay at Warning level.

No: Activate Auxiliary Relay at Alarm level
(default).

Automatic BIT

Yes: Perform Automatic & Manual Bit (default).

No: Perform Manual Bit only.

Alarm BIT

Yes: Successful Manual Bit activates the Alarm

Relay for approximately 3 seconds (default).

No: Successful Manual Bit does not activate the

Alarm Relay.

Auxiliary BIT**

Yes: Successful Manual Bit activates the

Auxiliary Relay for approximately 3 seconds
(default).

No: Successful Manual Bit does not activate the

Auxiliary Relay.

EOL**

Yes: Auxiliary Relay is used as End of Line.

No: Auxiliary Relay operates in accordance with
Function 2 and 5 (default).

Note: ** only available in Model 40/40L, LB, L4, L4B-4XXXX and 5XXXX

2.8.4 Heated Optics

The heated optics can be defined as one of the following modes:

Heated Mode

OFF: Not operated

On: Continuously

AUTO: Per temperature change

In AUTO mode, the default HEAT ON setting is 41°F (5°C). Heating stops

when the temperature is 27°F (15°C) above the start temperature.

You can define the start temperature below which the window will be
heated. The temperature can be defined between 32°F and 122°F (0°C to

50°C).