Table 20: contact ratings, Table 21: 20 ma current output – Spectrex 40/40L-LB UV/IR Flame Detector Series User Manual

Page 57

Advertising
background image

TM 40/40L, Rev (6) February 2013

Troubleshooting

45

wiring arrangement is identified on the detector by the
part number (see Model and Types on page 2).

Option 1: Power, RS-485, 0-20mA (Sink), Fault I
Relay (N.C), Alarm Relay, (N.O) (see Figure 7).

Option 2: Power, RS-485, 0-20mA (Source) and HART

protocol, Fault Relay (N.O), Alarm Relay, (N.O), (N.C).

Option 3: Power, RS-485, 0-20mA (Source) and HART

protocol, Fault Relay (N.O), Alarm Relay (N.O, N.C).

Option 4: Power, RS-485, Fault Relay (N.C), Auxiliary

Relay (N.O), Alarm Relay, (N.O).

Option 5: Power, RS-485, Fault Relay (N.O), Auxiliary
Relay (N.O), Alarm Relay, (N.O).

Electrical

Outputs

Dry Contact Relays

Table 20: Contact Ratings

Relay Name Type

Normal
Position

Maximum
Ratings

Alarm

SPDT

N.O., N.C.

2A at 30 VDC

Auxiliary

SPST

N.O.

2A at 30 VDC

Fault (see
Notes 1 and 2)

SPST

N.C. or N.O 2A at 30 VDC

Notes:
1. The Fault relay (in wiring options 1, 2, 4) is

normally energized closed during normal operation
of the detector. The relay is de-energized open if a
fault condition or low voltage situation occurs.

2. In wiring options 3, 5 the relay is normally

energized open during normal operation of the

detector. The relay is de-energized close contact if
a fault condition or low voltage situation occurs.

0-20mA Current Output: The 0-20mA can be Sink or

Source according to the wiring option source (see
General Instructions for Electrical Wiring on page 49).
The maximum permitted load resistance is 600Ω.

Table 21: 20 mA Current Output

State

Output

Fault

0 +1 mA

BIT Fault

2 mA ±10%

Normal

4 mA ±10%

IR

8 mA ±5%

UV

12 mA ±5%

Warning

16 mA ±5%

Alarm

20 mA ±5%

Advertising