Noise data, Easicool™ precision air conditioning, Technical data upflow units x type - 2 – Airedale EasiCool 6kW 64kW User Manual

Page 126

Advertising
background image

EasiCool™

Precision Air Conditioning

Technical Data Upflow Units X Type - 2

Noise Data

Sound

Frequency (Hz) dB

Measurement

Overall

dB(A)

63

125

250

500

1000

2000

4000

8000

V8X

Discharge Air

Power

78

71

75

74

73

73

72

65

60

Return Air

Power

63

68

71

63

58

59

53

48

41

Case Breakout

Power

63

68

71

63

58

59

53

48

41

Sound @ 3m

Pressure

49

53

57

49

43

44

39

33

26

V10X

Discharge Air

Power

81

74

78

77

76

76

75

68

63

Return Air

Power

66

71

74

66

61

62

56

50

43

Case Breakout

Power

66

71

74

66

61

62

56

50

43

Sound @ 3m

Pressure

51

56

61

52

46

47

41

36

29

V13X

Discharge Air

Power

78

72

75

73

73

73

72

65

60

Return Air

Power

63

69

71

63

58

59

53

48

42

Case Breakout

Power

63

69

71

63

58

59

53

48

42

Sound @ 3m

Pressure

48

54

57

48

43

44

38

34

27

V15X

Discharge Air

Power

74

71

76

73

70

69

68

63

58

Return Air

Power

62

68

72

63

56

56

49

48

42

Case Breakout

Power

62

68

72

63

56

56

49

48

42

Sound @ 3m

Pressure

47

53

57

48

41

42

35

34

27

V17X

Discharge Air

Power

78

75

79

77

74

73

71

67

62

Return Air

Power

65

72

75

67

59

59

53

51

44

Case Breakout

Power

65

72

75

67

59

59

53

51

44

Sound @ 3m

Pressure

50

57

61

52

44

44

38

36

30

V20X2

Discharge Air

Power

82

75

79

78

77

78

76

69

64

Return Air

Power

67

73

75

67

62

63

57

52

46

Case Breakout

Power

67

73

75

67

62

63

57

52

46

Sound @ 3m

Pressure

53

58

61

53

48

48

42

37

31

V22X2

Discharge Air

Power

86

80

84

82

81

82

80

73

68

Return Air

Power

71

77

80

71

66

67

61

55

49

Case Breakout

Power

71

77

80

71

66

67

61

55

49

Sound @ 3m

Pressure

57

62

65

57

52

52

46

41

35

V26X2

Discharge Air

Power

86

80

84

82

81

82

80

73

68

Return Air

Power

71

77

80

71

66

67

61

55

49

Case Breakout

Power

71

77

80

71

66

67

61

55

49

Sound @ 3m

Pressure

57

62

65

57

52

52

46

41

35

V28X

Discharge Air

Power

90

102

95

86

84

85

81

81

78

Return Air

Power

79

89

80

79

76

75

68

63

57

Case Breakout

Power

79

89

80

79

76

75

68

63

57

Sound @ 3m

Pressure

64

75

65

65

62

60

53

49

42

V28X2

Discharge Air

Power

90

102

95

86

84

85

81

81

78

Return Air

Power

79

87

80

79

76

74

67

63

57

Case Breakout

Power

79

87

80

79

76

74

67

63

57

Sound @ 3m

Pressure

64

73

65

65

61

60

53

49

42

126

EasiCool Technical Manual 7535776 V1.1.0_04_2013

Te

ch

ni

ca

l

X-

Ty

pe

22

0V

6

0H

z

V

(1) dB(A) is the overall sound level, measured on the A scale
(2) All sound data measured at nominal conditions, Discharge Air, Return air and case breakout is sound power.

Advertising