Easicool™ precision air conditioning, Technical data, Te ch ni ca l o utd oo r – Airedale EasiCool 6kW 64kW User Manual

Page 184: Performance data, Operating limit

Advertising
background image

EasiCool™

Precision Air Conditioning

Mean Condensing

Ambient

Temperature °C

25°C

30°C

35°C

40°C

45°C

48°C

Output kW Output kW Output kW Output kW Output kW Output kW

CR50

35

33.7

13.7

-

-

-

-

40

52.6

34

14.2

-

-

-

45

71.7

53.1

34.4

14.8

-

-

50

91.3

72.5

53.8

35.1

15.5

-

55

111.5

92.6

73.7

54.8

35.9

16.9

CR65

35

44.9

18.6

-

-

-

-

40

69.1

45.2

19.3

-

-

-

45

93.8

69.7

45.6

20

-

-

50

119.2

94.8

70.6

46.4

21

-

55

145.5

120.9

96.4

72

47.5

22.6

CR80

35

55.3

23

-

-

-

-

40

85.8

55.8

23.8

-

-

-

45

116.7

86.6

56.5

24.7

-

-

50

148.4

118.1

87.8

57.5

25.8

-

55

180.9

150.4

120

89.5

58.9

28.3

CR105

35

72.1

30

-

-

-

-

40

110.8

72.6

31

-

-

-

45

150.4

111.7

73.3

32.2

-

-

50

191.1

152.1

113.2

74.5

33.8

-

55

233.3

193.8

154.6

115.5

76.3

36.4

Technical Data

Performance Data

(1)

Output kW refers to the condenser heat rejection.

Standard Variable Speed Head Pressure Control
Minimum Ambient Air DB °C

-20°C

Maximum Ambient Air DB °C

+48

Optional On/Off Head Pressure Control
Minimum Ambient Air DB °C

-0°C

Maximum Ambient Air DB °C

+48

Operating Limit

(1)

For conditions outside those quoted, please contact Airedale.

(2)

Low ambient kits are available for applications with temperatures below those quoted, please contact Airedale.

184

EasiCool Technical Manual 7535776 V1.1.0_04_2013

Te

ch

ni

ca

l

O

utd

oo

r