Easicool™ precision air conditioning, Technical data, Te ch ni ca l o utd oo r – Airedale EasiCool 6kW 64kW User Manual

Page 188: Electrical data -1

Advertising
background image

EasiCool™

Precision Air Conditioning

CR50

CR65

CR80

CR105

Unit Data

(1)

Nominal Run Amps

A

5.8

5.8

8.7

8.7

Maximum Start Amps

A

11.2

11.2

16.8

16.8

Recommended Mains Fuse

A

10

10

16

16

Max Mains Cable Incoming

mm²

6

6

6

6

Mains Supply

230V / 1Ph + N / 60Hz

Fan - Per Fan

Quantity

2

2

3

3

Motor Size

kW

0.63

0.63

0.63

0.63

Full Load Amps

A

2.9

2.9

2.9

2.9

Locked Rotor Amps

A

5.6

5.6

5.6

5.6

OPTIONAL EXTRAS

Short Case Axial Fan - Per Fan

Quantity

2

2

3

3

Motor Size

kW

1.4

1.4

1.4

1.4

Full Load Amps

A

6

6

6

6

Locked Rotor Amps

A

18

18

18

18

EC Condenser Fan - Per Fan

Quantity

2

2

3

3

Motor Size

kW

0.77

0.77

0.77

0.77

Full Load Amps

A

3.3

3.3

3.3

3.3

Technical Data

Electrical Data -1

(1)

Nominal data based on 35°C ambient and a 50°C mean condensing temperature and using standard fan.

188

EasiCool Technical Manual 7535776 V1.1.0_04_2013

Te

ch

ni

ca

l

O

utd

oo

r

Advertising