Electrical data -2, Easicool™ precision air conditioning, Technical data – Airedale EasiCool 6kW 64kW User Manual

Page 189: Te ch nic al o utd oo r

Advertising
background image

EasiCool™

Precision Air Conditioning

Technical Data

Electrical Data -2

CR12

CR16

CR22

CR30

Unit Data

(1)

Nominal Run Amps

A

1.72

1.72

3.02

3.02

Maximum Start Amps

A

6.02

6.02

7.7

7.7

Recommended Mains Fuse

A

6

6

6

6

Max Mains Cable Incoming

mm²

6

6

6

6

Mains Supply

220V / 2Ph / 60Hz

Fan - Per Fan

Quantity

1

1

1

1

Motor Size

kW

0.39

0.39

0.64

0.64

Full Load Amps

A

1.72

1.72

3.02

3.02

Locked Rotor Amps

A

6.02

6.02

7.7

7.7

OPTIONAL EXTRAS

Short Case Axial Fan - Per Fan

Quantity

1

1

1

1

Motor Size

kW

0.82

0.82

1.75

1.75

Full Load Amps

A

3.5

3.5

7.8

7.8

Locked Rotor Amps

A

8.75

8.75

19.5

19.5

EC Condenser Fan - Per Fan

Quantity

1

1

1

1

Motor Size

kW

0.75

0.75

0.73

0.73

Full Load Amps

A

3.4

3.4

3.3

3.3

(1)

Nominal data based on 35°C ambient and a 50°C mean condensing temperature and using standard fan.