Easicool™ precision air conditioning, Technical data, Te ch ni ca l o utd oo r – Airedale EasiCool 6kW 64kW User Manual

Page 190

Advertising
background image

EasiCool™

Precision Air Conditioning

CR50

CR65

CR80

CR105

Unit Data

(1)

Nominal Run Amps

A

6.04

6.04

9.06

9.06

Maximum Start Amps

A

15.4

15.4

23.1

23.1

Recommended Mains Fuse

A

10

10

16

16

Max Mains Cable Incoming

mm²

6

6

6

6

Mains Supply

220V / 2Ph / 60Hz

Fan - Per Fan

Quantity

2

2

3

3

Motor Size

kW

0.64

0.64

0.64

0.64

Full Load Amps

A

3.02

3.02

3.02

3.02

Locked Rotor Amps

A

7.7

7.7

7.7

7.7

OPTIONAL EXTRAS

Short Case Axial Fan - Per Fan

Quantity

2

2

3

3

Motor Size

kW

1.75

1.75

1.75

1.75

Full Load Amps

A

7.8

7.8

7.8

7.8

Locked Rotor Amps

A

19.5

19.5

19.5

19.5

EC Condenser Fan - Per Fan

Quantity

2

2

3

3

Motor Size

kW

0.73

0.73

0.73

0.73

Full Load Amps

A

3.3

3.3

3.3

3.3

(1)

Nominal data based on 35°C ambient and a 50°C mean condensing temperature and using standard fan.

Technical Data

Electrical Data -2

190

EasiCool Technical Manual 7535776 V1.1.0_04_2013