Technical data, Easicool™ precision air conditioning, Operating limits – Airedale EasiCool 6kW 64kW User Manual

Page 56: Important

Advertising
background image

EasiCool™

Precision Air Conditioning

56

EasiCool Technical Manual 7535776 V1.1.0_04_2013

Technical Data

Moisture Content

Operating Band

Mo

ist

ure

C

on

ten

t k

g/k

g D

ry

Air

W

et

Bu

lb

Te

mp

era

tur

e (

°C

)

Dry Bulb Temperature (°C)

40

%

60

%

70

%

80

%

90

%

20%

10%

10

15

20

25

5

0

15

18

28

10

5

0

20

25

30

35

40

10

0%

50

%

Re

lat

ive

H

um

idi

ty

En

th

alp

y a

t s

at

ur

at

ion

(J

/g

D

ry

A

ir)

Nominal Design Operating Condition 24°C Dry Bulb 45% RH

Operating Limits

Indoor Air Temperature

+18°C to +28°C

Indoor RH%

+40% to +55% (Based upon 24°C Dry Bulb)

Outdoor Temperature

-20°C to +48°C

IMPORTANT

Fan Power Input (Fan Gain) must be added to the room load to establish full gross cooling capacity requirements.
Fan Power Input can be found in the mechanical data sections.
Fan Power Input is taken at the operating conditions based on 25Pa ESP.