EasiCool™

Precision Air Conditioning

CR12

CR16

CR22

CR30

Unit Data

(1)

Nominal Run Amps

A

1.1

1.1

2.9

2.9

Maximum Start Amps

A

2.8

2.8

5.6

5.6

Recommended Mains Fuse

A

6

6

6

6

Max Mains Cable Incoming

mm²

6

6

6

6

Mains Supply

230V / 1Ph + N / 60Hz

Fan - Per Fan
Quantity

1

1

1

1

Motor Size

kW

0.24

0.24

0.63

0.63

Full Load Amps

A

1.1

1.1

2.9

2.9

Locked Rotor Amps

A

2.8

2.8

5.6

5.6

OPTIONAL EXTRAS

Short Case Axial Fan - Per Fan
Quantity

1

1

1

1

Motor Size

kW

0.61

0.61

1.4

1.4

Full Load Amps

A

2.8

2.8

6

6

Locked Rotor Amps

A

7

7

18

18

EC Condenser Fan - Per Fan
Quantity

1

1

1

1

Motor Size

kW

0.7

0.7

0.77

0.77

Full Load Amps

A

3.1

3.1

3.3

3.3

Technical Data

Electrical Data -1

(1)

Nominal data based on 35°C ambient and a 50°C mean condensing temperature and using standard fan.