Easicool™ precision air conditioning, Noise data – Airedale EasiCool 6kW 64kW User Manual

Page 71

Advertising
background image

EasiCool™

Precision Air Conditioning

Sound

Frequency (Hz) dB

Measurement

Overall

dB(A)

63

125

250

500

1000

2000

4000

8000

V40X

Discharge Air

Power

94

113

99

92

89

84

85

85

83

Return Air

Power

83

98

84

85

82

74

71

68

61

Case Breakout

Power

83

98

84

85

82

74

71

68

61

Sound @ 3m

Pressure

68

84

69

71

67

59

56

53

46

V40X2

Discharge Air

Power

94

113

99

92

89

84

85

85

83

Return Air

Power

82

98

84

85

81

74

71

68

62

Case Breakout

Power

82

98

84

85

81

74

71

68

62

Sound @ 3m

Pressure

68

85

69

71

66

59

56

53

47

V45X2

Discharge Air

Power

94

113

99

92

89

84

85

85

83

Return Air

Power

83

98

84

85

83

74

71

68

62

Case Breakout

Power

83

98

84

85

83

74

71

68

62

Sound @ 3m

Pressure

69

84

69

71

68

59

57

53

47

V50X2

Discharge Air

Power

97

115

109

95

92

84

86

84

80

Return Air

Power

84

99

93

86

83

74

71

66

58

Case Breakout

Power

84

99

93

86

83

74

71

66

58

Sound @ 3m

Pressure

70

85

79

72

68

60

57

52

43

V55X2

Discharge Air

Power

97

115

109

95

92

84

86

84

80

Return Air

Power

84

99

93

86

83

74

72

66

58

Case Breakout

Power

84

99

93

86

83

74

72

66

58

Sound @ 3m

Pressure

70

85

79

72

68

60

57

52

43

V60X2

Discharge Air

Power

98

116

110

97

93

86

87

86

82

Return Air

Power

86

102

94

89

85

76

73

69

60

Case Breakout

Power

86

102

94

89

85

76

73

69

60

Sound @ 3m

Pressure

72

87

80

75

70

61

59

54

46

71

EasiCool Technical Manual 7535776 V1.1.0_04_2013

Te

ch

nic

al

X-T

yp

e

V

380

V

6

0H

z

Technical Data Upflow Units X Type

Noise Data

(1) dB(A) is the overall sound level, measured on the A scale
(2) All sound data measured at nominal conditions, Discharge Air, Return air and case breakout is sound power.

Advertising