Noise data - vertical, Easicool™ precision air conditioning, Sound data – Airedale EasiCool 6kW 64kW User Manual

Page 192: Te ch ni ca l o utd oo r

Advertising
background image

EasiCool™

Precision Air Conditioning

Sound

Overall

dB(A)

Frequency (Hz) dB

Measurement

63

125

250

500

1000

2000

4000

8000

CR12

Power

75

69

87

76

68

69

66

61

51

Pressure

@ 10m

44

37

56

45

37

38

34

30

20

CR16

Power

75

69

87

76

68

69

66

61

51

Pressure

@ 10m

44

37

56

45

37

38

34

30

20

CR22

Power

80

82

92

76

73

74

71

66

62

Pressure

@ 10m

49

50

61

44

42

43

40

35

30

CR30

Power

80

82

92

76

73

74

71

66

62

Pressure

@ 10m

49

50

61

44

42

43

40

35

30

CR50

Power

83

85

95

79

76

77

74

69

65

Pressure

@ 10m

52

53

64

47

45

46

43

38

33

CR65

Power

83

85

95

79

76

77

74

69

65

Pressure

@ 10m

52

53

64

47

45

46

43

38

33

CR80

Power

85

87

97

81

78

79

76

71

67

Pressure

@ 10m

54

55

65

49

47

48

44

40

35

CR105

Power

85

87

97

81

78

79

76

71

67

Pressure

@ 10m

54

55

65

49

47

48

44

40

35

Noise Data - Vertical

SOUND DATA

IMPORTANT

The sound data quoted is based on the unit having the STANDARD FAN running at FULL SPEED under normal
operating conditions.

For sound data of optional fan selections, please contact Airedale.

Measurement of Sound Data

All sound data quoted has been measured in the third-octave band limited values, using a Real Time Analyser calibrated
sound intensity meter in accordance with BS EN ISO9614 Part 1 : 1995.

All Sound Power Levels quoted are calculated from measured sound intensity according BS EN ISO9614 Part 1 : 1995.

Semi Hemispherical

Sound Pressure Levels are calculated from sound power using the semi-hemispherical method where the noise source
is in junction with 2 boundaries i.e. the floor and 1 wall.

192

EasiCool Technical Manual 7535776 V1.1.0_04_2013

Te

ch

ni

ca

l

O

utd

oo

r

Advertising