Technical data, Performance data, Easicool™ precision air conditioning – Airedale EasiCool 6kW 64kW User Manual

Page 183: Te ch nic al, Outd oo r, Operating limit

Advertising
background image

EasiCool™

Precision Air Conditioning

Mean Condensing

Ambient

Temperature °C

25°C

30°C

35°C

40°C

45°C

48°C

Output kW Output kW Output kW Output kW Output kW Output kW

CR12

35

8.8

3.3

-

-

-

-

40

13.8

8.8

3.4

-

-

-

45

19

14

8.9

3.6

-

-

50

24.4

19.2

14.1

9.1

3.8

-

55

29.8

24.7

19.5

14.4

9.3

4.1

CR16

35

11.9

5

-

-

-

-

40

18.2

12

5.2

-

-

-

45

24.7

18.4

12.1

5.4

-

-

50

31.3

25

18.6

12.3

5.6

-

55

38.2

31.8

25.4

19

12.6

6.5

CR22

35

15.4

6.2

-

-

-

-

40

24

15.5

6.4

-

-

-

45

32.8

24.2

15.7

6.7

-

-

50

41.7

33.1

24.6

16

7

-

55

51

42.3

33.7

25.1

16.4

7.7

CR30

35

19.8

8.1

-

-

-

-

40

30.6

20

8.4

-

-

-

45

41.7

30.9

20.2

8.7

-

-

50

53.1

42.1

31.3

20.5

9.2

-

55

64.8

53.8

42.8

31.9

21

9.8

Technical Data

Performance Data

(1)

Output kW refers to the condenser heat rejection.

Standard Variable Speed Head Pressure Control
Minimum Ambient Air DB °C

-20°C

Maximum Ambient Air DB °C

+48

Optional On/Off Head Pressure Control
Minimum Ambient Air DB °C

-0°C

Maximum Ambient Air DB °C

+48

Operating Limit

(1)

For conditions outside those quoted, please contact Airedale.

(2)

Low ambient kits are available for applications with temperatures below those quoted, please contact Airedale.

Te

ch

nic

al

183

EasiCool Technical Manual 7535776 V1.1.0_04_2013

O

utd

oo

r

Advertising