Easicool™ precision air conditioning, Technical data downflow units x type – Airedale EasiCool 6kW 64kW User Manual

Page 139

Advertising
background image

EasiCool™

Precision Air Conditioning

139

EasiCool Technical Manual 7535776 V1.1.0_04_2013

Te

ch

nic

al

X-T

yp

e

22

0V

6

0H

z

V

V40X-EZRE-2

V40X2-EZRE-2

V45X2-EZRE-2

Standard Condenser Match - X

CR65

CR65

CR80

Unit Data Full Function - X

(1)

Nominal Run Amps

A

157.6

156.6

167.1

Maximum Start Amps

A

414.9

323.8

330.5

Recommended Mains Fuse Size

A

200

200

200

Unit Data Cooling Only - X

(2)

Nominal Run Amps

A

78.9

77.9

88.4

Maximum Start Amps

A

336.2

245.0

251.8

Recommended Mains Fuse Size

A

100

100

100

Max Mains Incoming Cable Size

mm²

185

185

185

Mains Supply

V

220V / 3PH / 60HZ

Control Circuit

VAC

24

24

24

Evaporator Fan - Motor Per Fan

Centrifugal Forward Curved DD EC - Designed to 25Pa ESP

Maximum Electrical Input Power

(3)

kW

6.3

6.3

6.3

Full Load Amps

A

25.63

25.63

25.63

Locked Rotor Amps

A

197

197

197

Compressor - Per Compressor
Quantity x Motor Size

kW

1 x 16.07

2 x 8.26

2 x 9.19

Nominal Run Amps

A

46.72

22.9

26.6

Locked Rotor Amps

A

304

190

190

Type Of Start

Direct On Line

Standard Condenser Match - AC Motor - Per Fan
Electrical Input Power

kW

0.64

0.64

0.64

Full Load Amps

A

3.02

3.02

3.02

OPTIONAL EXTRAS
Electric Heating
Stage Of Reheat

3

3

3

Number Of Elements

12

12

12

Rating

kW

30

30

30

Current Per Phase

A

78.73

78.73

78.73

Humidifier
Capacity

kg/hr

15

15

15

Rating

kW

11.25

11.25

11.25

Full Load Amps

A

29.52

29.52

29.52

Evaporator Fan Options
Larger Fan Motor - AC Motor - Per Fan

Centrifugal Forward Curved AC - Designed to 25Pa ESP

Electrical Input Power

(3)

kW

N/A

N/A

N/A

Full Load Amps

A

N/A

N/A

N/A

Locked Rotor Amps

A

N/A

N/A

N/A

Standard Size Motor - EC Motor - Per Fan

Centrifugal Backward Curved DD EC - Designed to 25Pa ESP

Electrical Input Power

(3)

kW

2.63

2.63

2.63

Full Load Amps

A

9.8

9.8

9.8

Condenser Fan Options
Standard Condenser Motor - EC Motor - Per Fan
Electrical Input Power

kW

0.73

0.73

0.73

Full Load Amps

A

3.3

3.3

3.3

Technical Data Downflow Units X Type

Electrical Data

V40X - V45X2

Mechanical

(1)

Entering air 24°C/45% RH ambient 35°C.

(2)

Fan Gain / Fan power input based upon fan operating with design airflow at 25Pa ESP, These values may change with different ESP.

(3)

With Standard forward curved fan motors; Machine weight includes a refrigerant charge.

(4)

Backward curved EC fan options quote electrical power. All other options quote shaft power.

(5)

For refrigerant charges, refer to

Unit Refrigerant Charge (kg/Circuit)

.

(6)

Based on air temperature of 15.5°C leaving the evaporator coil.

(7)

Based upon low pressure hot water 82°C inlet / 71°C outlet. Air on 20°C. Refer to

Low Pressure Hot Water

.

Electrical

(1)

Values given for full function units (incl. electric heating, humidification and matched condenser) at 7°C evaporating and 54.4°C condensing with standard

forward curved fan motors, for optional data, please contact Airedale.

(2)

Values given for Cooling only units (incl. Compressor, evaporator fan and matched condenser) at 7°C evaporating and 54.4°C condensing, for optional

data, please contact Airedale.

(3)

Electrical input power relates to the maximum absorbed electrical power. Actual operating fan power input is shown in the mechanical data tables.