Precision Air Conditioning

Optional Extras General

Condensate Pump

Sizes 8 - 26

The condensate pump has a 3 litre reservoir with a capacity of 5 l/m at a head of 8m and is mounted in the unit base.

Sizes 28 - 60

The condensate pump has a 6 litre reservoir with a capacity of 5 l/m at a head of 10.8m and is mounted in the unit
base. The following graphs illustrate the TOTAL static (head) pressure available. The system horizontal pipe losses and
vertical lift should be factored in when calculating the condensate pump performance.

8 - 26

28-60

2

4

6

8

10

12

0

2

4

6

8

10

12

0

5

9

7

13

15

11

5

9

7

13

15

11

Pump Flow Rate (l/min)

Pump Flow Rate (l/min)

Head (m)

Head (m)

IMPORTANT
Use only 10mm (3/8”) copper tube when connecting the discharge stub to the condensate pump. The discharge line
from the pump should rise no more than 6 meters vertically and no more than 8 metres in total length before being
interrupted with a swan neck, air break and tundish.

A

B

C

D

A

Condensate Pump

B

Condensate pump discharge line; 10mm

(3/8”) copper tube; maximum vertical run

6m, maximum TOTAL run 8m

C

Swan Neck with Tundish

D

Drain line from Tundish, > 10mm (3/8”)

tube

(MUST BE copper tube when

coupled with humidifier drain),

minimum fall 1 : 20