Easicool™ precision air conditioning, Technical data downflow units x type, Electrical data v13x - v17x – Airedale EasiCool 6kW 64kW User Manual

Page 131

Advertising
background image

EasiCool™

Precision Air Conditioning

131

EasiCool Technical Manual 7535776 V1.1.0_04_2013

Te

ch

nic

al

X-T

yp

e

22

0V

6

0H

z

V

V13X-EZRE-2

V15X-EZRE-2

V17X-EZRE-2

Standard Condenser Match - X

CR22

CR22

CR30

Unit Data Full Function - X

(1)

Nominal Run Amps

A

47.4

49.0

52.6

Maximum Start Amps

A

151.8

153.7

190.7

Recommended Mains Fuse Size

A

63

63

63

Unit Data Cooling Only - X

(2)

Nominal Run Amps

A

27.7

29.3

33.0

Maximum Start Amps

A

132.1

134.0

171.0

Recommended Mains Fuse Size

A

32

40

40

Max Mains Incoming Cable Size

mm²

35

35

35

Mains Supply

V

220V / 3PH / 60HZ

Control Circuit

VAC

24

24

24

Evaporator Fan - Motor Per Fan

Centrifugal Forward Curved DD EC - Designed to 25Pa ESP

Maximum Electrical Input Power

(3)

kW

2.2

1.9

1.9

Full Load Amps

A

9.1

8

8

Locked Rotor Amps

A

22.8

20

20

Compressor - Per Compressor
Quantity x Motor Size

kW

1 x 5,53

1 x 6.57

1 x 7.82

Nominal Run Amps

A

15.6

18.3

21.9

Locked Rotor Amps

A

120

123

160

Type Of Start

Direct On Line

Standard Condenser Match - AC Motor - Per Fan
Electrical Input Power

kW

0.64

0.64

0.64

Full Load Amps

A

3.02

3.02

3.02

OPTIONAL EXTRAS
Electric Heating
Stage Of Reheat

1

1

1

Number Of Elements

3

3

3

Rating

kW

7.5

7.5

7.5

Current Per Phase

A

19.68

19.68

19.68

Humidifier
Capacity

kg/hr

3

3

3

Rating

kW

2.25

2.25

2.25

Full Load Amps

A

5.90

5.90

5.90

Evaporator Fan Options
Larger Fan Motor - AC Motor - Per Fan

Centrifugal Forward Curved AC - Designed to 25Pa ESP

Electrical Input Power

(3)

kW

N/A

N/A

N/A

Full Load Amps

A

N/A

N/A

N/A

Locked Rotor Amps

A

N/A

N/A

N/A

Standard Size Motor - EC Motor - Per Fan

Centrifugal Backward Curved DD EC - Designed to 25Pa ESP

Electrical Input Power

(3)

kW

1.01

1.01

1.01

Full Load Amps

A

3.2

3.2

3.2

Condenser Fan Options
Standard Condenser Motor - EC Motor - Per Fan
Electrical Input Power

kW

0.73

0.73

0.73

Full Load Amps

A

3.3

3.3

3.3

Technical Data Downflow Units X Type

Electrical Data

V13X - V17X

Mechanical

(1)

Entering air 24°C/45% RH ambient 35°C.

(2)

Fan Gain / Fan power input based upon fan operating with design airflow at 25Pa ESP, These values may change with different ESP.

(3)

With Standard forward curved fan motors; Machine weight includes a refrigerant charge.

(4)

Backward curved EC fan options quote electrical power. All other options quote shaft power.

(5)

For refrigerant charges, refer to

Unit Refrigerant Charge (kg/Circuit)

.

(6)

Based on air temperature of 15.5°C leaving the evaporator coil.

(7)

Based upon low pressure hot water 82°C inlet / 71°C outlet. Air on 20°C. Refer to

Low Pressure Hot Water

.

Electrical

(1)

Values given for full function units (incl. electric heating, humidification and matched condenser) at 7°C evaporating and 54.4°C condensing with standard

forward curved fan motors, for optional data, please contact Airedale.

(2)

Values given for Cooling only units (incl. Compressor, evaporator fan and matched condenser) at 7°C evaporating and 54.4°C condensing, for optional

data, please contact Airedale.

(3)

Electrical input power relates to the maximum absorbed electrical power. Actual operating fan power input is shown in the mechanical data tables.

Advertising