Bulletin f-9-pux2, Key to display the analog input/ output screen – Dwyer PSX2 User Manual

Page 104

Advertising
background image

95

(1) Select “ANALOG INPUT/OUTPUT” on the SYS-

TEM screen.
Press the

ENT

key to display the ANALOG INPUT/

OUTPUT screen.

10.3.2 “ANALOG INPUT/OUTPUT”: when performing analog input/output

and calibration

This function allows you to set the analog input/output and perform input/output calibration.

AI ch2

AO

AI ch1

Red

(+)

Red

(+)

Black

(

í)

Black

(

í)

4 to 20mA

AO

(Output)

Indicator,
recorder,
regulator, etc.

(Note) The connector should
be connected to AI/AO.

Analog output: 4 to 20mA DC 1 point “Load resistance under 600

Ÿ”

Analog input: 4 to 20mA DC 1 point “Input resistance 200

Ÿ”

4 to 20mA DC 1 point “Input resistance 200

Ÿ” or

1 to 5V DC 1 point

Analog input/output cord (page 20)

− +

AI

(Input)

Bulletin F-9-PUX2