10.2.2 Logger data fi le format

One logger fi le is composed of fi les of two types indicated below. The data fi le is stored as
divided by 65,500 lines for permitting high-speed access and due to restrictions in the maximum
number of lines of CSV display of Microsoft Excel.

File type

File name

Remarks

Confi guration fi le

(Logging name)_(date)_(hour).ini

Means logger start time and relevant logger
data fi les.

Data fi le

(Logging name)_(date)_(hour).ini

Logging data in a specifi c period

The maximum number of data fi les in a logger is 20 fi les in case of a continuous logger, and is
550 fi les in case of an appointed time logger. The appointed time logger is of one fi le per day.
Note) After reaching the maximum data fi le, the logging will be stopped.

The logger data list shows the following names excluding extension (.ini) of logger confi gura-
tion fi les.
• Logger … “Logger name_(start date)_(start hour)”
• Quick logger … “QUICK__(start date)_(start hour)”

If capacity shortage arises during logging operation, logging operation stops with the following
screen displayed.
When this screen appears, replace the SD memory card immediately.
Press the

ESC

key, or remove SD memory card, the message will be cleared.

Move the cursor to “STOP” to stop logging, press the

ENT

key, and once remove the memory

card.

Bulletin F-9-PUX2