10.3.3 “CALORIE MODE”: when measuring consumed heat quantity

This function calculates the heat quantity received and sent with liquid (water) in cooling and
heating.

(1) Select “CALORIE MODE” on the SYSTEM screen.

Press the

ENT

key to display the CALORIE MODE

screen.

(2) Make each setting on the CALORIE MODE screen.

(For details, refer to the setting contents in the fol-
lowing page.)

Heat

source

Load

Detector
(type : PSX2)

Converter

Converter

Q: Flow rate of the

heating medium

T2: Temperature of the heating

medium of the receiving side

T1: Fluid temperature (inlet)

PUX2

Consumed heat quantity
q = K · Q · (T1–T2)
K : heat quantity

conversion factor

(For heating K = 4.123,
For cooling = 4.186)

Temperature
sensor

Temperature
sensor

AI/AO