SSC Series condensing pressure

with 95ºF (35ºC) condenser air

R-22 = 260 psi (1,793 kPa/17.93 bars)

Note: Due to the variables involved in remote air-cooled condenser installations, no set or

standard piping procedure exists. Each installation must be designed and installed by
qualified persons. Follow the instructions supplied with the condenser.


3-11 Checking Motor Direction

Compressor

Note:

• Never switch contactor leads or motor leads for reversing

rotation.

• Do not use contactor or motor leads for phase matching.
• Compressor noise from reverse rotation is noticeable. Do not

run in this mode for more than ten (10) seconds. The
compressor shuts off if run longer in this mode.

• Reverse rotation can cause suction and discharge pressures to

be approximately equal; amp draws will be lower than normal.

• If you discover that compressor rotation is reversed, correct it

by switching any two main power leads into the disconnect
switch or distribution block
on the unit.

Water Pump

A positive pressure of 20 to 30 psi (137.9 to 206.8 kPa/1.38 to 2.07
bars) on the

TO PROCESS

line indicates correct pump rotation.


Condenser Fan

On SSC Series remote air-cooled units, air should draw through
the condenser and discharge up from the condenser.

Changing fan rotation direction

• Disconnect and lock out power at the fused disconnect.
• If all fans are going backwards, reverse any two main power

leads.

• If only some of the fans are going backwards, switch any two of

their respective motor leads.