6 determining flow rate, 7 shutdown – Sterlco S Series Central Chilling Stations User Manual

Page 38

Advertising
background image

Page 38 of 86

SSC Series Central Chilling Stations

Note: If the recirculation pump does not turn on (or that the flow switch is not satisfied) the

compressors will not be allowed to turn on.

6. Check the pump(s) amp draws and pressures. The amp

draws must be within the pump(s) running load and service
factor amps.

7. Operate the chiller, looking for leaks and listening for

unusual noises or vibrations that could indicate improper
operation.

8. Check condenser fans for pressure switch settings as shown

in the table below:

Fan

Set on

Set off

number

psi kPa bars psi kPa bars

1

not applicable; Fan 1 is a variable-speed fan

2 240

1,654.8

16.5

190

1,310.1

13.1

3 265

1,827.2

18.3

215

1,482.4

14.8

4 285

1,965.1

19.7

235

1,620.3

16.2

5 305

2,102.9

21.1

255

1,758.2

17.6


5-6 Determining

Flow

Rate

To determine flow:

1. Close the gauge cock leading to the pump suction side and

open the gauge cock leading to the pump discharge.

2. Start the pump and make note of the discharge pressure in

psi (kPa/bars).

3. Check the pump curve for the appropriate horsepower

pump at the discharge pressure psi.

4. Project this point down to find the flow in gpm (lpm).

5. Process pumps can be left wide open if running amps are

below full load amps.

5-7 Shutdown

1. Ready process and related equipment for shut down.

2. Turn off main power.

3. Close the water make up valve.

4. If the system is to be drained, open the 2” drain valve.