Page 28 of 86

SSC Series Central Chilling Stations

4-5 Chilled Water Circuit

If your central chilling station is equipped with the optional
integral pump tank, make the process cooling water supply
connection at the P1 manifold at the left side of the pump tank at
the exposed connection. Bring the process cooling water return
connection to the

Hot

well of the tank on the right side at the

flanged connection.

Warm coolant (water and ethylene glycol mixture) returns from the
process to the tank, then gets pumped through the evaporator
where it is cooled. The coolant flows to the process and returns to
repeat the cycle.

4-6 Refrigeration

Circuit

• SSC Series chilling station air- and water-cooled unit

refrigeration cycles differ only in the way the compressed gas
is condensed to a liquid.

• Liquid refrigerant from the condenser passes through a shut-off

valve into a filter/dryer.

• The refrigerant then passes through the sight glass and solenoid

valves into the thermal expansion valve which regulates flow;
the valve lowers pressure and boiling point. Heat from the fluid
causes the refrigerant to boil off into a vapor.

• The refrigerant vapor flows through the suction line back into

the compressor.

• The refrigerant gives up heat as it re-condenses to a liquid in

the condenser.


4-7 Freezestat

Control

The freezestat shuts down the compressor if the chilled water
temperature approaches the freezing point. The chilled water pump
on the system will continue to run. It is factory-set at 40°F (4ºC) or
10°F (6ºC) below the rated capacity operating temperature of 50°F
(10ºC).