If you want lower chilled water temperatures, you’ll need to mix
process water with industrial- (not automotive) grade ethylene or
propylene glycol with rust inhibitor to provide protection down to
20°F (12ºC) below the operating temperature you want. Figure 3
below shows the proper mixtures needed to provide protection to
20°F (12ºC) below the operating temperature you want. You can
then reset the freezestat cutout temperature to a temperature 10°F
(6ºC) below the operating temperature you selected.


Caution!

Make sure all freezestat adjustments are performed

by a qualified refrigeration service technician.

The Sterling product warranty does not cover system freeze-up!


Figure 3

Freezing Protection Curve

Ethylene glycol required for evaporator freeze protection