9-3 Evaporator

Maintenance

The evaporator(s) may be accessed for back-flushing by removal
of the 2” plug (approx. 51 mm) in the return control nipple and the
flow switch in the supply control nipple. If the suggested piping
recommendations have been followed, one circuit of a multiple
circuit chiller may be back-flushed without shutting down the
entire system. Check Y-strainer for any clogging.

9-4 Pump

Motor

Seal

Pump seals require water for lubrication, so the pump(s) must
never be run dry. Always fill the tank before attempting to operate
the pump(s). Seal failures usually follow a period of dry operation
of the pump.


9-5 Makeup

Valve

Periodically inspect the water makeup valve assembly for proper
operation. If the valve no longer shuts off completely or reliably,
replace it. The plastic ball float should be buoyant for proper
operation.


9-6 Recommended Pump Tank Spare Parts

Part no.

Part description

Quantity

A0550190

Pressure gauge

1 per pump

A0102396

Float valve, 1” (approx. 25 mm)

1 per tank

A0069538

Plastic ball float, 6” (approx. 152 mm)

1 per tank

A0102394

Float rod, 10” (25 cm)

1 per tank

- Call Sterling

Parts -

Pump seal and casing gasket

1 per pump

Check your Customer Information Packet for a complete list of
spare parts and part numbers for your SSC Series chilling station.