Gas Requirements

M414905

36

© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT

Turn on gas and check all pipe connections (internal

and external) for gas leaks with a non-corrosive leak

detection fluid. Purge air in gas service line by

operating the tumblers in the drying mode. If burner

does not light and unit goes into lockout, open and

close the door and restart. Repeat these steps until

burner ignites. Use pipe compound, resistant to

actions of L.P. gas, on all pipe threads.

Figure 18

WARNING

Check all pipe connections, internal and

external, for gas leaks using a non-

corrosive leak detection fluid. To reduce

the risk of explosion or fire, DO NOT USE

AN OPEN FLAME TO CHECK FOR GAS

LEAKS! Gas connections should be

checked twice a year for leakage.

W635

TMB2007N

1

Gas Line to Tumbler

2

Shut-Off Valve

3

Gas Supply Piping System

4

Gas “T” Fitting

5

6 in. (152 mm) Minimum Gas Pipe

6

Gas Pipe Cap

7

Sediment Trap

8

Suppply Pressure Tap