Gas Supply Pipe Sizing and Looping

Figure 19

TMB2126N

1

Gas furnace (120,000 Btu/hr.)

7

Minimum Pipe Size is 0.5 in. (12.7 mm)

2

Gas water heaters (400,000 Btu/hr. each)

8

25 ft. (7.6 m)

3

Gas space heaters (70,000 Btu/hr. each)

9

Main regulator

4

Sediment traps, supply pressure taps and

10

Gas meter

shut-off valves. Refer to Figure 18.

11

Pressure regulator (if required)

5

1 in. (25.4 mm) gas pipe loop

12

50 pound tumblers (120,000 Btu/hr each)

6

19 ft. (5.8 m)

75 pound tumblers (165,000 Btu/hr each)
F75 pound tumblers (215,000 Btu/hr each)

SAMPLE CALCULATIONS:

Equivalent length = Total length of main gas supply pipe to the far end of the tumblers.

= 25 ft. + 19 ft. (7.6 m + 5.8 m) gas supply pipe
= 44 ft. (13.4 m) Total Gas Line

Total Btu/hr.

= The sum of the Btu/hr. of all 50 pound tumblers being fed by the main gas supply pipe.
= 9 x 120,000
= 1,080,000 Btu/hr.

Using Table 5, the main supply pipe diameter should be 2 in. (51 mm).

IMPORTANT: Gas loop piping must be installed as illustrated to equalize gas pressure for all tumblers

connected to single gas service. Other gas using appliances should be connected upstream from loop.