evc/epc Controller

With SAE J1939 Interface

Output A or B Coil Settings

Select Coil B Active for a Dual

Coil Valve Control.

Enter minimum, maximum

current and dither frequency
according to the valve
specification.

Enter UP or DOWN ramp times.

“Change Settings” to apply the
changes to the unit’s temporary
memory.

Once the system is running, fine

tune these settings.

Always Active (ON)

– Output A is always active and cannot be set “OFF”.

Coil B

– active (ON/OFF) – Enables/Disables Output B.

Current feedback (ON/OFF)

When Current Feedback is “ON”, coil current output is monitored and adjusted proportionally to the demand
within the coil max and min settings.

Current Feedback compensates for supply voltage and coil temperature changes. When disabled,

the output’s

waveform is adjusted proportionally to the demand between 0% and 100% PWM Duty Cycle.

Inverted (ON/OFF)

When Inverted is “ON”, the output is inversely proportional to the input. This is used with normally closed valves.

When Inverted

is “OFF”, the output is proportional to the input.