023-00354-Rev1.6

evc/epc User Manual

35

Copyright © High Country Tek, Inc.

– 2013

evc/epc Controller

With SAE J1939 Interface

Dual Output With Over Speed Protection

It works with dual fixed displacement pumps and switches valves ON or OFF according to the measured RPM.

The measured engine RPM can be from the

alternator

‘R’ terminal, PPU, or SAE J1939.

BOTH outputs are ON when below

‘A’ setting.

When the measured RPM ≥ Set-point A RPM,
coil A ramps down to minimum current.

When the measured RPM ≥ Set-point B RPM,
coil B ramps down to minimum current

NOTE: with Ramps set to minimum times, the
outputs will drive ON/OFF valves