evc/epc Controller

With SAE J1939 Interface

Global Settings

Enable Auto-Reverse (On/Off)

When in HP Management or Anti-Stall

mode, if the measured RPM is ≤ RPM Stop
or No Load RPM
, coil A current ramps
down to 0, and then coil B current ramps up
to the Reverse Set- point.

The module will try to restart normal

operation after the reverse cycle completes.

Reverse Time (0 to 65 Sec)

– It sets the time that coil B will remain in reverse during an Auto-Reverse cycle.

Reverse Retry Count (0 to 65535)

–The number of times the Auto-Reverse cycle will try to restore normal RPM

before declaring a fault and disabling the unit.

Reverse set-point (0 to 100%)

– The percentage of Imax output current for coil B during the reverse cycle.

Fixed set-point (0 to 100%)

The percentage of Imax output current for coil A when the measured RPM is above the RPM slow or Max Load

RPM

in “anti-stall with fixed command” or “HP management with fixed command”.



Recover from loss of signal

When

ON”, the evc/epc automatically recovers and returns to normal operation after the pulse input and the

analog input(s) are back in range.

The evc/epc automatically recovers from a SAE J1939 message timeout error.

The evc/epc automatically recovers when the reference voltages or the supply voltages are outside the

acceptable limits and recover.

The evc/epc will not automatically recover from a coil open or short error.



Hard stop if disabled

When “ON”, coil A or B outputs are immediately set to zero without ramps whenever the enable input is set to
OFF”.

When “OFF”, the coil A or B outputs ramp down to zero when the enable input is set to “OFF”.