BTS Aisle Containment Manual, Rev. 1.0

___

December 2013

Chatsworth Products

14


3. Use Mounting Brackets to attach extrusions to the ceiling or to the tops of cabinets.

• Position the extrusions

so Gusset Joiners
face the outside of the
containment/duct.

• Mounting brackets

attach to the outside of
the containment/duct.

• Support extrusions on

both sides of Joiner
Gussets and close to
the ends of the duct.

• Space brackets

approximately every
48” (1200 mm) of
span.

• Use 3/8” threaded rod

to support the duct
from the ceiling as
shown.

• When cabinets are the

same height, you can
support extrusion(s)
directly from the tops
of cabinets.

• Flip the Mounting

Bracket and use a 3/8”
hex bolt to attach the
extrusion directly to
the tops of cabinets.

• Hardware for ceiling or

cabinet attachment is
not included.