6. Cut two vertical extrusions per corner. Each vertical extrusion should be 3.25” (83

mm) less than the cabinet to ceiling distance to allow space for the top of the duct
frame. Attach the extrusions in the corners with Plate Gussets as shown below.

• After the duct frame is

complete, you will
attach Corner Covers
around the outside of
the corner extrusions.