46

For GF-Series GlobalFrame Gen 1 Cabinets that are taller than the door frame assembly,
mount the bracket assembly as shown below. Attach the top bracket to the cabinet with the
M8 nut, from the Rail Support Bracket kit, onto the stud. The bottom bracket is attached to
the door top rail using one of the pre-installed M6 bolts in the rail and a M6 nut and washer.
Attach the bracket cover to the bottom bracket with two M4x6 screws.

For GF-Series GlobalFrame Gen 1 Cabinets that are shorter than the door frame assembly,
mount the bracket assembly as shown below; the picture is shown from the back side of the
door. Attach the top bracket to the cabinet with the M8 nut, from the Rail Support Bracket
kit, onto the stud. The bracket is attached to the door top rail using one of the pre-installed
M6 bolts in the rail and a M6 nut and washer. The bracket cover is not needed in this type of
installation.