function. Note that Mapped_Throttle is inverted; lowering its value (making
it more negative) increases the PD_Throttle value.

The Dither function adds and subtracts from the current command to

the PD based on PD_Dither_Percent, at a rate set by PD_Dither_Period.

The dithered current command is compared to the present PD_Current

and the error is fed into a PI controller. The feedback gains are set by the param-
eters PD Kp (proportional gain) and PD Ki (integral gain). The output of the
PI controller becomes the driver’s pulse width modulation, thus controlling the
average current of the driver. The final output is the VCL variable PD_Output,
which is displayed in the 1311 Monitor

»

Inputs menu as PD PWM.

The following PD processing variables are accessible by VCL:

VCL

VARIABLE

ACCESS

DESCRIPTION

Mapped_Throttle

Read Only

Command from throttle section

VCL_PD_Throttle

Read/Write

VCL-accessible PD command

PD_Throttle

Read Only

Resultant command to the PD

PD_Current

Read Only

Average current flowing in the PD

PD_Output

Read Only

Resultant PWM at PD output

7 — VCL

Fig. 16

Proportional driver processing.