3 — PROGRAMMABLE PARAMETERS:

Battery Parameters

BATTERY MENU, cont’d

ALLOWABLE

PARAMETER

RANGE

DESCRIPTION

Reset Volts Per Cell

0.90–3.00 V

The reset voltage level is checked only once, when KSI is first turned on.

BDI_Reset_Volts_Per_Cell

900–3000

Note that the BDI Reset Percent parameter also influences the algorithm
that determines whether BDI Percentage is reset to 100%.

Reset Volts Per Cell should always be set higher than Full Volts Per

Cell.

Reset Voltage Level = Reset Volts Per Cell × number of cells in the

battery pack.

*

Full Volts Per Cell

0.90–3.00 V

The full voltage level sets the Keyswitch Voltage that is considered to be

BDI_Full_Volts_Per_Cell

900–3000

100% state-of-charge; when a loaded battery drops below this voltage,
it begins to lose charge. Keyswitch Voltage is viewable in the 1311 menu
Monitor

»

Battery.

Full Voltage Level = Full Volts Per Cell × number of cells in the battery

pack.

*

Empty Volts Per Cell

0.90–3.00 V

The empty voltage level sets the Keyswitch_Voltage that is considered to

BDI_Empty_Volts_Per_Cell

900–3000

be 0% state-of-charge.

Empty Voltage Level = Empty Volts Per Cell × number of cells in the

battery pack.

*

Discharge Time

0–600 min.

Sets the minimum time for the BDI algorithm to count down the BDI

BDI_Discharge_Time

0–600

Percentage from 100% to 0%. The BDI algorithm integrates the time the
filtered keyswitch voltage is below the state of charge voltage level. When
that cumulative time exceeds the Discharge Time / 100, the BDI Percentage
is decremented by one percentage point and a new state of charge voltage
level is calculated.

State of Charge Level = ((Full Voltage Level - Empty Voltage Level)

× BDI Percentage / 100) + Empty Voltage Level.

BDI Reset Percent

0–100 %

When a battery has a high BDI percentage, its float voltage at KSI On

BDI_Reset_Percent

0–100

can sometimes cause false resets. The BDI Reset Percent parameter
addresses this problem by allowing the user to define a BDI Percentage
value above which the BDI Percentage variable will not reset.

When KSI is first powered on, the BDI Percentage variable will reset

to 100% only if ((Keyswitch Voltage > Reset Voltage Level) and (BDI
Percentage < BDI Reset Percent)).

* To determine the number of cells in your battery pack,
divide your Nominal Voltage setting (page 55) by 2.

DUAL DRIVE MENU

FOR DUAL DRIVE PARAMETERS, SEE THE DUAL DRIVE ADDENDUM, P/N 37022-DD.