To add automatic fault actions to the VCL faults, the VCL program-

mer must define the desired fault actions by using the sixteen VCL variables:
User_Fault_Action_01 through User_Fault_Action_16. Each of the UserFault
bits has a corresponding User_Fault_Action_xx variable (where “xx” is the
number of the VCL fault bit). When a VCL fault bit is set, the actions defined
in the corresponding User_Fault_Action_xx variable will be automatically
executed by the operating system. Here are the fault actions available in the
User_Fault_Actions_xx variables:

VARIABLE

FAULT

ACTION

User_Fault_Action_xx
*

Bit0 = ShutdownMotor

Disable the motor

*

Bit1 = ShutdownMainContactor Shut down the main contactor

(only if Main Enable = On)

*

Bit2 = ShutdownEMBrake

Shut down the EM brake

(only if EM Brake Disable Upon

Fault = On)

*

Bit3 = ShutdownThrottle

Set the Throttle_Command = 0%

*

Bit4 = ShutdownInterlock

Set the Interlock_State = Off

*

Bit5 = ShutdownDriverl

Shut down Driver1

*

Bit6 = ShutdownDriver2

Shut down Driver2

*

Bit7 = ShutdownDriver3

Shut down Driver3

*

Bit8 = ShutdownDriver4

Shut down Driver4

*

Bit9 = ShutdownPD

Shut down Proportional Driver

*

Bit10 = FullBrake

Set the Brake_Command = 100%

*

Bit11 = ShutdownPump

Shut down DC pump

*

Bit12 = TrimDisable

Disable Dual Drive trim

calculation.

*

Bit13 = SevereDual

For Dual Drive system, one con-

troller has a severe fault but

the main contactor must stay

closed so the other controller

can continue to operate.

*

Bit14 = ShutdownSteer

Steer angle = 0°

*

Bit15 = LOSDual

For Dual Drive system, set the

max speed to Dual_LOS_Max_Speed

parameter for operation in

Limited Operating Strategy.

The User_Fault_Action_xx variables should be set up at the beginning of a
VCL program (before the main loop) as these fault actions should be defined
only once in a program. Here is another example:

User_Fault_Action_02 = 24 ;Set fault action to ShutdownInterlock

;and ShutdownThrottle

MainLoop:
if (BDI_Percentage < 10)

{

UserFault1.2 = ON

;Set User Fault bit

Put_Spy_Text(“BDI Low”) ;Send message to Model 840 display

}

else

{

UserFault1.2 = OFF

;Clear User Fault bit

}

goto MainLoop

This time when UserFault1.2 is set, the operating system will ShutdownInterlock
and ShutdownThrottle (which will result in a Throttle_Command = 0%) in