106

Curtis 1234/36/38 Manual,

OS

11

7 — VCL

ENABLE_EMER_REV()

This function is used to engage emergency reverse using VCL. The 1311 EMR
Type must be set to = 1 in order for the Enable_Emer_Rev() function to operate.
If the system emergency reverse state is enabled (EMR_State bit variable = On),
the emergency reverse function will operate according to the Emergency Reverse
parameter settings; see page 59. To view the current emergency reverse state, see
the 1311 menu Monitor

»

Inputs: Emer Rev.

When the EMR_Type is set to = 1 and neither the Enable_Emer_Rev() nor the

Disable_Emer_Rev() function has been called, the state for emergency reverse is
Off (EMR_State bit variable = Off).

Syntax

Enable_Emer_Rev()

Parameters

None.

Returns

0 – Emergency reverse not enabled.

1 – Emergency reverse successfully enabled.

Error Codes

None.

Example

Enable_Emer_Rev()

This will enable the emergency reverse function.

DISABLE_EMER_REV()

This function is used to disengage emergency reverse using VCL. The 1311 EMR
Type must be set to = 1 in order for the Disable_Emer_Rev() function to operate.
If the system emergency reverse state is disabled (EMR_State bit variable = Off),
the emergency reverse function will stop operating and normal motor control func-
tion will resume (including an HPD/SRO check if the HPD/SRO Enable parameter
is set to On). To view the current emergency reverse state, see the 1311 menu
Monitor

»

Inputs: Emer Rev.

When the EMR_Type is set to = 1 and neither the Enable_Emer_Rev() nor the

Disable_Emer_Rev() function has been called, the state for emergency reverse is
Off (EMR_State bit variable = Off).

Syntax

Disable_Emer_Rev()

Parameters

None.

Returns

0 – Emergency reverse not disabled.

1 – Emergency reverse successfully disabled.

Error Codes

None.

Example

Disable_Emer_Rev()

This will disable the emergency reverse function.