8 — DIAGNOSTICS & TROUBLESHOOTING

Table 5 TROUBLESHOOTING CHART

PROGRAMMER LCD DISPLAY

CODE

EFFECT OF FAULT

POSSIBLE CAUSE

SET/CLEAR CONDITIONS

12

Controller Overcurrent

1. External short of phase U,V, or W

Set: Phase current exceeded the current

ShutdownMotor;

motor connections.

measurement limit.

ShutdownMainContactor;

2. Motor parameters are mis-tuned.

Clear: Cycle KSI.

ShutdownEMBrake;

3. Controller defective.

ShutdownThrottle;

FullBrake;

ShutdownPump.

13

Current Sensor Fault

1. Leakage to vehicle frame from phase Set: Controller current sensors have

ShutdownMotor;

U, V, or W (short in motor stator).

invalid offset reading.

ShutdownMainContactor;

2. Controller defective.

Clear: Cycle KSI.

ShutdownEMBrake;

ShutdownThrottle;

FullBrake;

ShutdownPump.

14

Precharge Failed

2. External load on capacitor bank (B+ Set: Precharge failed to charge the capacitor

ShutdownMotor;

connection terminal) that prevents

bank to the KSI voltage.

ShutdownMainContactor;

the capacitor bank from charging.

Clear: Cycle Interlock input or use VCL

ShutdownEMBrake;

1. See Monitor menu » Battery:

function

Precharge()

.

ShutdownThrottle;

Capacitor Voltage.

FullBrake;

ShutdownPump.

15

Controller Severe Undertemp

1. See Monitor menu » Controller:

Set: Heatsink temperature below -40°C.

ShutdownMotor;

Temperature.

Clear: Bring heatsink temperature

ShutdownMainContactor;

2. Controller is operating in an extreme above -40°C, and cycle interlock or KSI.

ShutdownEMBrake;

environment.

ShutdownThrottle;

FullBrake;

ShutdownPump.

16

Controller Severe Overtemp

1. See Monitor menu » Controller:

Set: Heatsink temperature above +95°C.

ShutdownMotor;

Temperature.

Clear: Bring heatsink temperature

ShutdownMainContactor;

2. Controller is operating in an extreme below +95°C, and cycle interlock or KSI.

ShutdownEMBrake;

environment.

ShutdownThrottle;

3. Excessive load on vehicle.

FullBrake;

4. Improper mounting of controller.

ShutdownPump.

17

Severe Undervoltage

1. Battery Menu parameters are

Set: Capacitor bank voltage dropped

Reduced drive torque.

misadjusted.

below the Severe Undervoltage limit

2. Non-controller system drain on battery. (see page 55) with FET bridge enabled.

3. Battery resistance too high.

Clear: Bring capacitor voltage above

4. Battery disconnected while driving.

Severe Undervoltage limit.

5. See Monitor menu » Battery:

Capacitor Voltage.

6. Blown B+ fuse or main contactor

did not close.