background image

4

WARNING

This appliance must be earthed. Failure to do so may result in electric shock and death.

The Oven must be connected to a separate electrical supply installed by a qualified and approved electrician. A

suitably rated isolating switch with a 3mm contact gap on both poles should be fitted for each oven installed.

establishments with standard ( Type ‘B’ ) circuit breakers are sensitive to ‘surges’ which occur on switching on

freezers, refridgerators and other catering equipment, including microwave ovens. Because of this, we strongly

recommend that a separate Type ‘C’ circuit breaker ( designed specifically for this type of equipment ) must be

fitted. An individual, suitably rated circuit breaker should be fitted for each oven installed.

If you are in any doubt about your electrical

supply, seek the advice of a qualified electrician

WARNING:

SINGLE PHASE

TWIN PHASE

Twin Phase models should be connected as

shown.

The Circuit Breaker should be rated at 16A/Phase

(TypeC).

SINGLE PHASE

UK models are fitted with a Blue 32Amp Plug to

BS4343

The Circuit Breaker should be rated at 45A

(TypeC).

TWIN PHASE

ELECTRICAL SUPPLY

EQUIPOTENTIAL

An equipotential earth point is provided on the rear panel of the oven for independent

earth (GnD) connection

WARninG: HiGH leAKAGe CURRenT earth connection is essential

POWER SUPPLY: EARTH LEAKAGE CIRCUIT BREAKERS

If the oven is connected to an Earth Leakage Circuit Breaker device, this should allow a

minimum of 30 milliamps earth current without interupting the circuit