3‐10 Receiving & Installation

MN2408

Transfer Switch Considerations

The following are general considerations for the safe use of a transfer switch:

1.

The transfer switch should be located inside the building near the main breaker box or
the disconnect box.

2.

The transfer switch must be kept away from any location that might allow water to get
on it.

3.

If the transfer switch is mounted outside, it must be protected from the environment and
it's elements.

4.

Do not mount the transfer switch on the generator set.

5.

Do not mount the transfer switch where flammable liquids or vapors are present.

Figure 3‐4 Basic Power Transfer System

Utility Power

Generator Power

L1

L2

N

Main Panel

Fuses or

Circuit

Breakers

Transfer
Switch

Mechanical

Interlock

L1

L2

N

Fuses or

Circuit

Breakers

Power To Load

L1

L2

N

Remote Start

Contact

Earth
Ground

Ground

Ground

Remote Start
Connect the remote start start contact (from transfer switch) to GLC Remote Start terminals.

Single Phase Power Connections

Output power connections must be fused within 25 feet of the generator. If the wires to the
transfer switch are shorter than 25 feet, connect L1, L2 and N to the transfer switch being sure to
follow NEC and local codes. If the wires to the transfer switch are longer than 25 feet, UL
requires that branch circuit protection be provided.
Power connections are made at L1, L2, Neutral and Ground points indicated in the Customer
Connections area shown in Figure 3‐5.