Operation 4‐3

MN2408

Digital Engine Controller Description EM0046A21 (MRS17) Continued

Table 4‐9 Manual Mode Sequence Description

Menu

Status

Condition of Transition

Action



Next State

Main

Measurement

Ready

Start request

PRESTART on,
Prestart time counter started

PRESTART

RPM > 2 or Oil pressure detected or
Gen voltage > 10V

Stop (Stop fail)

OFF mode selected or Shut down alarm active

Not Ready

Not Ready

RPM < 2, Oil pressure not detected, Vgen < 10V,
no shutdown alarm active, other than OFF mode
selected

Ready

Prestart

Prestart time elapsed

STARTER on, FUEL SOLENOID on,
MaxCrank time counter started

Cranking

Cranking

RPM> Start RPM

STARTER off, PRESTART off

Starting

D+ input activated or oil pressure detected or
Gen voltage > 25% Vgnom

STARTER off, PRESTART off

Cranking

MaxCrank time elapsed, 1st attempt

STARTER off, FUEL SOLENOID off,
STOP SOLENOID on,
CrankFail pause timer started

Crank pause

MaxCrank time elapsed, last attempt

STARTER off, PRESTART off

Shutdown (Start fail)

Crank Pause

CrankFail pause elapsed

STARTER on, FUEL SOLENOID on,
STOP SOLENOID off,
MaxCrank time counter started

Cranking

Starting

30% Nominal speed reached

READY TO LOAD on,
MaxStabTime counter started

Running

Running

Stop request

READY TO LOAD off,
Cooling time timer started

Cooling

RPM = 0 or any other shutdown condition

READY TO LOAD off,
FUEL SOLENOID off

Shutdown

Loaded

RPM = 0 or any other shutdown condition

FUEL SOLENOID off, STOP SOLENOID
on, READY TO LOAD off

Shutdown

Cooling

Cooling time elapsed

FUEL SOLENOID off,
STOP SOLENOID on

Stop

RPM = 0 or any other shutdown condition

FUEL SOLENOID off,
STOP SOLENOID on

Shutdown

Start request

READY TO LOAD on

Running

Stop

RPM = 0, Oil pressure not detected, Vgen < 10V

Ready

60 sec. Elapsed

Stop (Stop fail)



Some output

conditions are optional and may require additional programming of field

connection.

See appropriate wiring diagram.

Adjustment Menu
The adjustment menu, Figure 4‐10 allows setting engine and generator values such as
Passwords, Pre-Start Time, Crank Time, Cool Down Time, Alarm Conditions and values,
Shutdown Conditions and values, power transfer settings, etc.

Figure 4‐10 Adjustment Menu

> ENGINE BASIC

ENGINE PROT
GEN BASIC
GEN PROTECT

Use

Y and B to move the cursor to the desired parameter.

Press ENTER to select the parameter group.
Press PAGE to move to the next page of menu items.

Alarm List
Shows the active alarms and warnings. Press fault reset to clear the list.
ECU Alarm List
Shows the active ECU (engine control unit) fault codes. Press ENTER + fault reset to clear the
list.