Section 4
Operation

Operation 4‐1

MN2408

Digital Engine Controller Description

EM0046A21 (MRS17)

Figure 4‐8 Operator Control Panel

Stop

Manual

Run

Display

Menu
Group

LED Indicators

Operating Modes and

Horn & Fault Reset

Note: The operator control panel is equyipped with a heater element that allows the LCD display

to operate to -40

°C (not the entire generator set, see generator specifications). This

heater operates from the main battery power.

LED Indicators

Alarm (red) - Alarm (shutdown) condition occurred. Annunciates & shuts down generator.
Not In Auto (red) - Control is not in auto mode and cannot provide standby power.
Running (green) - Generator is running, no alarms or warnings.
Warning (yellow) - A warning condition has occurred. Annunciates only.
Ready/Auto (green) - Control is in Auto mode and ready to provide standby power.
Supplying Load (green) - Generator is providing output voltage to load.

Table 4‐8 Alarm & Warning Conditions

Alarm

Warning

X

X

High Coolant temperature

X

X

Low Oil pressure

X

X

Low Fuel level

X

X

Generator Under/Over Voltage

X

X

Generator Under/Over Frequency

X

X

Generator Over Current

X

Generator Overspeed

X

Coolant temperature Low

X

Starting battery Under/Over Voltage

Manual Run

Immediately begins the crank cycle to start engine and produce power (MAN mode only).

Start

Start generator set operation (MAN mode only).

Stop

Stops the Engine and generator set (MAN mode only).

Display

Displays setpoints, adjustments, Alarms and Warning conditions and Operating Mode selections.

Page

Changes menu displayed - Measurement, Adjustment or History.

Mode

A and "

Allows selection of OFF - MAN - AUTO mode choices.

Horn Reset

Deactivates the Horn output.

Fault Reset

Reset Alarms and Warnings.

Y and B

Selects the menu choice, select the setpoint or select the menu or increase/decrease the
setpoint value.

Enter

Confirm and accept changed setpoint value.

Enter +

Y and B Adjusts display contrast.

Enter+ Fault Reset Clears engine ECU faults.