4‐4 Operation

MN2408

Alarms

Following alarms are available:

Sensor fail (FLS) see Table 4‐10

Sensor fail is detected when measured value is 6% out of selected sensor characteristic.
Sensor fail is indicated by ##### symbol instead measured value.

Warning (WRN) see Table 4‐10

When warning comes up, only alarm outputs and common warning output are closed.

Shut down (SD) see Table 4‐10

When the shut-down alarm comes up, InteliLite opens outputs GCB CLOSE/OPEN, FUEL
SOLENOID, STARTER and PRESTART to stop the engine immediately. Alarm outputs and
common shutdown output are closed. Active or not reset protection disables start.

Table 4‐10 Possible Warnings

Events specification

Protection type

Wrn Oil press

WRN

Sd Oil press

SD

Wrn Water temp

WRN

Sd Water temp

SD

Wrn Wtemp Low

WRN

Wrn Fuel Level

WRN

Sd Fuel Level

SD

Battery voltage <, >

WRN

Battery flat

SD

Start fail

SD

Vgen <, >

SD

Vgen unbl

SD

Fgen <, >

SD

Igen unbl

SD

Overload

SD

RPM over

SD

RPM under

SD

PickupFault

SD

Stop fail

SD

WrnServiceTime

WRN

Emergency Stop

SD

ECU Common Warning

WRN

ECU Shutdown

SD