4‐8 Operation

MN2408

Table 4‐15 Engine Setpoints

Continued

Cooling time

Runtime of the unloaded gen-set to cool the engine before stop.
Step: 1s; Range: 0 - 3600 s

AfterCoolTime

Runtime of engine after cooling pump. Binary output Cooling pump is
closed when the engine starts and opens AfterCool time delayed after
gen-set stops. Step: 1s Range: 0 - 3600s

CoolingSpeed

Selects the function of the Binary output IDLE/NOMINAL during engine
Cooling state.
NOMINAL : Cooling is executed at Nominal speed and generator
protections are active.
IDLE: Cooling is executed at Idle speed and generator protections are
switched off.
Hint: Binary output IDLE/NOMINAL must be configured and connected to
speed governor. Engine Idle speed must be adjusted on speed governor.

D+ function

ENABLED: The D+ terminal is used for both functions “running engine”
detection and charge fail detection.
CHRGFAIL: The D+ terminal is used for charge fail detection only
DISABLED: The D+ terminal is not used.
Note: Magnetization current is independent of this setpoint value.

Table 4‐16 Engine Protect Setpoints

ECUFreqSelect

This setpoint should be used only for Volvo and Scania engines.

ECU Speed Adjust

This setpoint should be used only for Volvo and Scania engines.

WTBF Accept RPM

The WtBfAcceptRPM delay setpoint will start to count down since
cranking. Controller waits before communicating with the ECU for this
time. This is because the JD engine passes some erroneous RPM signals
during the first 500ms. Step: 0,1s Range: 0 - 3s

Eng prot del

During the start of the gen-set, some engine protections have to be
blocked (e.g. Oil pressure). The protections are unblocked after the
Protection del time. The time starts after reaching Start RPM.
Step: 1s; Range: 0 - 300 s

Horn timeout

Max time limit of horn sounding. Set to zero if you want to leave the output
HORN open. Step: 1s; Range: 0 - 600 s

Overspeed

Threshold for over speed protection.
Step: 1% of nominal RPM; Range: 100 - 150%

Wrn Oil press

Warning threshold level for ANALOG INPUT 1.
Step: 1 psi; Range: Sd Oil press - 10000

Sd Oil press

Shutdown threshold level for ANALOG INPUT 1.
Step: 1 psi; Range: -100 - Wrn Oil press

Oil press del

Delay for ANALOG INPUT 1. Step: 1 s; Range: 0 - 180

Sd Water temp

Warning threshold level for ANALOG INPUT 2.
Step: 1

°C; Range: Wrn Wtemp - 10000

Wrn Water temp

Warning threshold level for ANALOG INPUT 2.
Step: 1

°F; Range: Wrn Wtemp low - Sd Water temp

Wrn Wtemp low

Warning threshold level for low value on ANALOG INPUT 2.
Step: 1

°F; Range: -100 - Wrn Water temp

Water temp Low del

Delay for ANALOG INPUT 2 Wrn Wtemp low. Step: 1 s; Range:1-180 s

Water temp del

Delay for ANALOG INPUT 2 alarm. Step: 1 s; Range: 0 - 180 s

Wrn Fuel Level

Warning threshold level for ANALOG INPUT 3.
Step: 1 %; Range: Sd Fuel Level - 10000

Sd Fuel Level

Shutdown threshold level for ANALOG INPUT 3.
Step: 1 %; Range: -100 - Wrn Fuel Level

Fuel Level del

Delay for ANALOG INPUT 3. Step: 1 s; Range: 0 - 180 s

Batt overvolt

Warning threshold for high battery voltage.
Step: 0,1 V; Range: Batt undervolt - 40V

Batt undervolt

Warning threshold for low battery voltage.
Step: 0,1 V; Range: 8V - Batt overvolt

Batt volt del

Delay for low battery voltage alarm. Step: 1s; Range: 0 - 600 s

NextServTime

Counts down when engine running. If reaches zero, an alarm appears.
Step: 1h; Range: 0 -65535h