4‐10 Operation

MN2408

Table 4‐18 Sensor Spec Setpoints

Calibr AI1,AI2, AI3

Calibrating constant to adjust the measured value of IL analog inputs.
Physical dimension of calibrating constant is corresponding to Analog
input. Step: 1; Range: -1000 to +1000

AnOut-kW/20mA

Conversion coefficient from gen-set power to iG-IOM or PTM analog
output. Step: 1; Range: 1 to 32000

Table 4‐19 IOM/PTM Module Setpoints

AnlInIOM1 lev1

The level for IOM ANALOG INPUT 1 alarm detection.
Step: 1; Range: -100 to +10000

AnlInIOM1 lev2

The level for IOM ANALOG INPUT 1 alarm detection.
Step: 1; Range: -100 to+10000

AnlInIOM1 del

Delay for IOM ANALOG INPUT 1 alarm. Step: 1 s; Range: 0 - 180 s

AnlInIOM2 lev1

The level for IOM ANALOG INPUT 2 alarm detection.
Step: 1; Range: -100 to +10000

AnlInIOM2 lev2

The level for IOM ANALOG INPUT 2 alarm detection.
Step: 1; Range: -100 to +10000

AnlInIOM2 del

Delay for IOM ANALOG INPUT 2 alarm. Step: 1 s; Range: 0 - 180 s

AnlInIOM3 lev1

The level for IOM ANALOG INPUT 3 alarm detection.
Step: 1; Range: -100 to +10000

AnlInIOM3 lev2

The level for IOM ANALOG INPUT 3 alarm detection.
Step: 1; Range: -100 to +10000

AnlInIOM3 del

Delay for IOM ANALOG INPUT 3 alarm.
Step: 1 s; Range: 0 - 180 s

AnlInIOM4 lev1

The level for IOM ANALOG INPUT 4 alarm detection.
Step: 1; Range: -100 to +10000

AnlInIOM4 lev2

The level for IOM ANALOG INPUT 4 alarm detection.
Step: 1; Range: -100 to +10000

AnlInIOM4 del

Delay for IOM ANALOG INPUT 4 alarm. Step: 1 s; Range: 0 - 180 s
The protection of IOM/PTM inputs is activated by over crossing the limits.

Calibr AInIOM 1..4

Calibrating constant to adjust the measured value of IOM/PTM analog
inputs. Physical dimension of calibrating constant is corresponding to
Analog input. Step: 1; Range: -1000 to +1000