Baldor GLC40 User Manual

Page 49

Advertising
background image

Operation 4‐9

MN2408

Table 4‐17 Generator Protect Setpoints

Overload

Threshold for generator overload (in % of Nominal power)
Step: 1% of Nominal power; Range: 0 - 200%

Overload Wrn

Threshold for generator overload warning (in % of Nominal power)
Step: 1% of Nominal power; Range: 0 - 200%

Overload del

Delay for generator overload alarm. Step: 0.1s; Range: 0 - 60.0 s

Ishort

Shutdown occurs when short circuit limit Ishort limit is reached.
Step: 1 % of Nominal current; Range: 100 - 500 %

2Inom del

IDMT curve shape selection. 2Inom del is Reaction time of IDMT
protection for 200% overcurrent Igen = 2* Nominal current.
Step: 0,1 s; Range: 0,1 - 20 s
IDMT is “very inverse” generator over current protection. Reaction time is
not constant but depends on generator over current level according
following formula. Reaction time is limited up to 900 sec = 15 minutes.
IDMT protection is not active for Reaction time values longer than 15
minutes.

ReactionĂTimeĂ

+ 2lnomĂdelĂ *Ă NominĂcurrent

lgenĂ

*Ă NominĂcurrent

Curr unbal

Threshold for generator current asymmetry (unbalance).
Step: 1% of Nominal current; Range: 1 - 100% of Nominal current

Curr unbal del

Delay for generator current assymetry. Step: 0.1 s; Range: 0 - 60.0 s

Gen >V

Shutdown level for generator overvoltage. All three phases are checked.
Maximum out of three is used.
Step: 1% of Nominal voltage; Range: Gen >V Wrn -200%

Gen >V Wrn

Warning level for generator overvoltage. All three phases are checked.
Maximum out of three is used.
Step: 1% of Nominal voltage; Range: Gen <V Wrn - Gen >V

Gen <V Wrn

Warning level for generator under voltage. All three phases are checked.
Minimum out of three is used.
Step: 1% of Nominal voltage; Range: Gen <V - Gen >V Wrn

Gen <V

Shutdown level for generator under voltage. All three phases are checked.
Minimum out of three is used.
Step: 1% of Nominal voltage; Range: 0% - Gen <V Wrn

Gen V del

Delay for generator under voltage and over voltage alarm
Step: 0.1s; Range: 0 - 60 s

Volt unbal

Threshold for generator voltage unbalance alarm.
Step: 1% of Nominal voltage; Range: 0 - 100% of Nominal voltage

Volt unbal del

Delay for generator voltage unbalance alarm.
Step: 0.1s; Range: 0 - 60.0 s

Gen >f

Shutdown level for generator over frequency.
Step: 0.1% of Nominal frequency; Range: Gen > Wrn - 200.0%

Gen >f Wrn

Warning level for generator over frequency.
Step: 0.1% of Nominal frequency; Range: Gen <f Wrn - Gen >V

Gen <f

Shutdown level for generator under frequency.
Step: 0.1% of Nominal frequency; Range: 0.0 - Gen <f Wrn

Gen <f Wrn

Warning level for generator under frequency.
Step: 0.1% of Nominal frequency; Range: Gen <f - Gen >f Wrn

Gen f del

Delay for generator under frequency and over frequency alarm.
Step: 0.1s; Range: 0 - 60.0 s

Advertising
This manual is related to the following products: