Baldor GLC40 User Manual

Page 71

Advertising
background image

Operation 4‐31

MN2408

Figure 4‐17 Main Menu Loop Parameters

Parameter

Setting

Range

System Voltage (Line To Line)

XXXXX VAC

120-15000V AC

System Frequency

50Hz/60Hz

Toggle Between 50/60 Hz

System Phases

1 Phase/3 Phase

Toggle Between 1 & 3 Phase

Neutral Connected

Toggle Between Yes/No

Voltage Sensing

Voltage Sensing Pt Ratio

Ratio XXX

Enter Number 1-208 (1=Direct)

Current Sensing

Current Sensing Ct Ratio

Ratio XXX

Enter Number 1-999 (1=Direct)

Temperature Scale

Deg C/Deg F

Toggle Between Deg C/Deg F

Pressure Scale

PSI/KPA

Toggle Between Psi/Kpa

Start Delay

XXX Seconds

0-999 Seconds

Crank Time

XX Seconds

0-99 Seconds

Rest Time

XX Seconds

0-99 Seconds

Starter Re-engage Delay

XX Seconds

0-99 Seconds 0=Disabled

Number Of Cranks

XX Cranks

0-99 Times 0=Continuous

Bypass Delay

XX Seconds

0-99 Seconds

Cool down Delay

XX Seconds

0-9999 Seconds

Nominal RPM

XXXX RPM

0-4000RPM

Flywheel Teeth (Engine Speed
Sensing, Magnetic Pick Up

XXX Teeth

0-999 Teeth

Crank Disconnect

XX %

0-100%

Overspeed

XX %

100-150%

Overspeed Transient

X.X Seconds

0.0-9.9 Seconds

Run Output

Fail Safe Yes/No

Toggle Between Yes/No

Loss Of Speed Signal

Shutdown Alarm/Shutdown

Toggle Between Alarm/Shutdown

Common Fail For

Not In Auto Yes/No

Toggle Between Yes/No

Horn For Not In Auto

Toggle Between Yes/No

Prog Output #1

Common Fail (Factory setting)

Prog Output #2

Common Fail (Factory setting)

Prog Output #3

Common Fail (Factory setting)

Prog Output #4

Common Fail (Factory setting)

Prog Output #5

Common Fail (Factory setting)

Prog Output #6

Common Fail (Factory setting)

Warm-up Delay

0-99 Seconds

Neutral Delay

0-99 Seconds

Return Delay

0-999 Seconds

Reset Run Hours

Access by Master Password Only

Yes/No

Toggle Between Yes/No