Operation 4‐19

MN2408

Analog Faults

Eight analog fault inputs are user programmable for 12 fault conditions. Each analog fault input requires a specific analog
signal type.

Fault
Name

Fault
Action

Inputs
Signal

Low Engine Temperature

Alarm

Engine Temperature

High Engine Temperature #1

Alarm

Engine Temperature

High Engine Temperature # 2

Shutdown

Engine Temperature

Low Oil Pressure #1

Alarm

Oil Pressure

Low Oil Pressure #2

Shutdown

Oil Pressure

Low Battery Voltage

Alarm

Battery Voltage

High Battery Voltage

Alarm

Battery Voltage

Weak Battery

Alarm

Battery Voltage

Undervoltage

Shutdown

Voltage

Under frequency

Shutdown

AC Frequency

Low Engine Temperature

An analog DC signal is provided from an engine mounted sender. The low engine temperature fault is activated when engine
temperature is below a pre-determined setpoint for a specified time delay. This fault is programmable for temperature
setpoint level, transient time delay settings and other functions.

High Engine Temperature #1 An analog DC signal is provided from an engine mounted sender. The high engine temperature fault is activated when

engine temperature is above a pre-determined setpoint for a specified time delay. This fault is programmable for the level of
temperature setpoint, transient time delay settings and other functions.

High Engine Temperature # 2 An analog DC signal is provided from an engine mounted sender. The high engine temperature fault is activated when the

engine temperature rises above a pre-determined setpoint for a specified time delay. This fault is programmable for the level
of temperature setpoint, transient time delay settings and other functions.

Low Oil Pressure #1

An analog DC signal is provided from an engine mounted sender. The low oil pressure alarm fault is activated when the oil
pressure is below a pre-determined setpoint for a specified time delay. This fault is programmable for pressure setpoint level,
transient time delay settings and other functions.

Low Oil Pressure #2

An analog DC signal is provided from an engine mounted sender. The low oil pressure shutdown fault is activated when the
oil pressure is below a pre-determined setpoint for a specified time delay. This fault is programmable for pressure setpoint
level, transient time delay settings and other functions.

Low Battery Voltage

The low battery voltage alarm fault is activated when the battery voltage drops below a pre-determined setpoint for a
specified time delay. This fault is programmable for the voltage setpoint level, transient time delay settings and other
functions.

High Battery Voltage

The high battery voltage alarm fault is activated when the battery voltage rises above a pre-determined setpoint for a
specified time delay. This fault is programmable for voltage setpoint level, transient time delay settings and other functions.

Weak Battery

The weak battery alarm fault is activated when the battery voltage drops below a pre-determined setpoint for a specified
time delay. The weak battery alarm detects a low capacity (i.e. “weak“) battery condition during the cranking cycle. The weak
battery alarm is programmed for a lower battery voltage setpoint and shorter time delay than the low battery alarm function.
This fault is programmable for voltage setpoint level, transient time delay settings and other functions.

Undervoltage

All 3-phases of the generator output are monitored for an undervoltage condition. The undervoltage sensor is programmable
for type of fault action (alarm or shutdown), pickup and dropout voltage setpoints (i.e. adjustable hysteresis) and transient
time delay settings.

Under frequency

The generator output is monitored for an under frequency condition. The under frequency sensor is programmable for type of
fault action (alarm or shutdown), frequency setpoint, and transient time delay settings.

Engine Speed Analog Input

A magnetic pickup (engine speed sensor) measures engine speed. The engine speed sensor allows the controller to perform
the following control functions:

Overspeed shutdown
Crank Disconnect control
Loss of speed signal detection
Starter Re-engage control
RPM display