4‐22 Operation

MN2408

Timer Countdown Timer countdown menus are automatically displayed when a specific time delay function

occurs during a control sequence. When a time delay begins, the LCD display will show the time
delay function name (i.e. Engine Start Delay) and the current time remaining in the countdown
sequence. When the timing function has expired, the LCD display will automatically change to
either the next timing sequence countdown display or return to the original system status menu.

Action

Description

Display

Comments

Apply Power and
Reset faults.

Main LCD Display.

Vavg

000

Aavg

000

Freq

000

Show Operating Status screens

ENGINE START

DELAY 45 SEC

Displays specific time delay function
name and remaining time.

Other time delay functions are:

ENGINE START

DELAY 45 SEC

CRANK PERIOD

XX SEC

REST PERIOD

XX SEC

STARTER RE-ENGAGE

DELAY XX SEC

BYPASS

DELAY XX SEC

COOLDOWN

DELAY XXXX SEC

WARMUP

DELAY XX SEC

RETURN

DELAY XX SEC

NEUTRAL

DELAY XX SEC

Note: Countdown screens only appear if Utility/Gen Ready To Load outputs are programmed.