Removing brocade mlxe-32 router dc power supplies, Figure 104 – Brocade Communications Systems Brocade MLX Series and Brocade Netlron XMR 53-1002373-02 User Manual

Page 157

Advertising
background image

Brocade MLX Series and Brocade NetIron XMR Hardware Installation Guide

139

53-1002373-02

Installing a Brocade MLXe-32 router

2

CAUTION

For the NEBS-compliant installation of 32-slot routers with AC and DC systems, use a ground wire
of at least 2 American Wire Gauge (AWG). The ground wire should have an agency-approved
crimped connector (provided with the device) attached to one end, with the other end attached to
building ground. The connector must be crimped with the proper tool, allowing it to be connected
to both ground screws on the enclosure. Before crimping the ground wire into the provided
ground lug, ensure the bare copper wire has been cleaned and antioxidant is applied to the bare
wire.

CAUTION

To ensure adequate bonding when attaching the ground lug, a minimum of 20 PSI of torque is
required to be applied to the mounting hardware used to attach the ground lug.

FIGURE 104

Crimping the power supply wire in the lug

4. Reconnect the power lugs to the power supply unit.

5. Connect the -48V wire to the negative terminal and the 0V wire to the positive terminal.

NOTE

DC return must be isolated from the router ground (DC-I) when making connections to the
connections to the power supply.

6. Replace the safety cover. Refer to

Figure

.

This equipment installation must meet NEC/CEC code requirements. Consult local authorities for
regulations.

Removing Brocade MLXe-32 router DC power supplies

Follow these steps to remove a 2400W DC power supply in a Brocade MLXe-32 router:

1. Ensure the main DC power breaker is OFF.

2. Use a #1 Phillips screwdriver to remove screw that secures the safety cover, as shown in

Figure 102

on page 138. Remove the safety cover.

3. Use a #2 Phillips screwdriver to remove the screws securing the power lugs. Refer to

Figure 103

on page 138.

4. Pull down on handle to remove power supply. Refer to

Figure 100

on page 136.

1 AWG power supply wire:

for 2400W power supply, use#4 AWG
for 3000W power supply, use #2 AWG

2

Power lug

2

1

1

2

Advertising