Manually setting the fan speed, Monitoring the cooling system, Changing the temperature polling interval – Brocade Communications Systems Brocade MLX Series and Brocade Netlron XMR 53-1002373-02 User Manual

Page 354

Advertising
background image

336

Brocade MLX Series and Brocade NetIron XMR Hardware Installation Guide

53-1002373-02

Managing the cooling system

7

Changing the temperature polling interval

By default, the router reads the temperature sensor on each module every 60 seconds. To change
the polling interval, enter the temp-poll-period command at the global CONFIG level of the CLI.

Brocade(config)# temp-poll-period 120

Syntax: temp-poll-period <seconds>

For the <seconds> parameter, you can specify a value from 30 – 120.

NOTE

Adjusting temperature polling interval out of the default setting can negatively affect the efficient
cooling of blades and may cause a blade to overheat and shutdown.

Manually setting the fan speed

Typically, the management module, in conjunction with default settings of low and high
temperature thresholds, determines the speed of the two four-speed fans. (For information about
changing the low and high temperature thresholds, refer to

“Changing temperature thresholds for

modules and fan speeds”

on page 331.) You can manually set the fan speed using the

set-fan-speed command in the Global CONFIG level of the CLI.

NOTE

Auto control of fan speed is not monitored when cards are in interactive mode. Set fan speed to high
to prevent over-temp condition.

NOTE

Setting a value other than auto or high disables auto fan control and will negatively affect the
efficient cooling of blades and may cause a blade to overheat and shutdown.

For example, to set the speed of fan 0 to medium-high, enter the following command.

Brocade# set-fan-speed med-high

Syntax: set-fan-speed <fan-speed>

For the <fan-speed> parameter, you can specify the following:

auto – The system is adjusted by the monitoring system.

high – The system sets the fan speed to high.

low – The system sets the fan speed to low.

med – The system sets the fan speed to medium.

med-high – The system sets the fan speed to medium-high.

Monitoring the cooling system

You can monitor the following aspects of the router cooling system:

The temperature of the fan control modules

The status and speed of the fans

The temperature warnings sent to the system log and that generate an SNMP trap