4 Electrical connection

Errors during initialization

Startup

The checks described above complete the process of installation and electrical connection. For
startup, use the additional documentation (operating manual or system manual).
The "Introduction" section of this document contains an overview of all documentation for the
measuring, control, and automation system.

If

Then

After the LED test,

the "Status" LED lights up in red and

the "BusError" LED does not light up

There is an internal error and the central process-
ing unit must be replaced.

After the LED test,

the "Status" LED flashes red and

the "BusError" LED does not light up

The internal buffer battery is dead and must be
replaced.

For buffer battery replacement, please contact
the device manufacturer or plant installer.